Electrical
& Software Control Systems for Safe Rides & Shows |
(407) 290-2000 |
This is the setup information for connecting a modem to a Allen-Bradley SLC 500. We have tested this setup with a 14,400 and a 57k USRobotics modem. The Modem to SLC cable is a standard off the shelf 25-to-9 pin serial cable.
|
USRobotics |
|
SLC Communications Setup |
||||
|
1 |
DN |
DTR Override |
|
Computer/Terminal Address |
7 |
|
|
2 |
UP |
Verbal Result Codes |
|
HW Type |
S/03,S/04,CH0,1770-KF3,1747-K3 |
|
|
3 |
DN |
Display Result Codes |
|
Online Wait for Reply Timeout |
15 seconds |
|
|
4 |
UP |
Echo Offline Command |
|
Communication Port |
COM1 |
|
|
5 |
UP |
Auto Answer |
|
Baud |
9600 |
|
|
6 |
UP |
Carrier Detect Normal |
|
Parity |
None |
|
|
7 |
DN |
Load Factory Settings |
|
Error Checking Mode |
CRC |
|
|
8 |
UP |
Dumb Mode |
|
Protocol |
Full Duplex |
|
|
|
|
Dial |
Yes |
|||
|
|
|
|
||||
|
CH0 Sys |
|
|
||||
|
Communication Driver |
DF1 Full Duplex |
|||||
|
Baud Rate |
9600 |
|||||
|
Stop Bits |
1 |
|||||
|
Duplicate Packet Detection |
Enabled |
|||||
|
ACK Timeout (x20ms) |
50 |
|||||
|
Control Line |
No Handshaking |
|||||
|
Source ID |
9 |
|||||
|
Parity |
None |
|||||
|
Error Detection |
CRC |
|||||
|
Max Retries |
3 |
|||||
|
ENQ Retries |
3 |
|||||
|
Embedded Response |
Enabled |
|||||
| www.birket.com | P.O. Box 610190, Ocoee, FL 34761-0190 | fax (407) 654-2150 |